Skip to content
VTEKE

Converters

VT Series — Single-Phase Voltage Transducer

ModelVT

Product overview

The VTEKE VT Series consists of single-phase True RMS voltage transducers designed to convert AC voltage signals into proportional DC analog outputs. The series provides voltage measurement for industrial monitoring and control applications, with multiple analog output configurations and AC or DC auxiliary supply options.

Applications

  • Industrial automation and control systems
  • PLC analog input applications
  • Electrical voltage monitoring
  • Energy management and monitoring systems
  • Electrical distribution panels
  • AC voltage signal conversion

Key features

  • True RMS voltage measurement
  • Conversion of AC voltage into proportional DC analog signals
  • Multiple voltage input ranges
  • Current and voltage analog output options
  • AC and DC auxiliary power supply versions
  • Galvanic isolation on AC-powered models
  • LED operating status indication
  • DIN rail mounting

Specifications

Electrical Characteristics

Electrical Characteristics
Auxiliary Supply — DC Model24 V DC (9–34 V DC)
Auxiliary Supply — AC Model220 V AC (85–280 V AC)
Galvanic Isolation — DC ModelNot isolated
Galvanic Isolation — AC Model1.5 kV isolation, 3.0 kV withstand
Max. Power Consumption — DC Model1 W (35 mA) at 24 V DC
Max. Power Consumption — AC Model2 W (20 mA) at 115 V AC / 3 W (15 mA) at 230 V AC

Measurement Characteristics

Measurement Characteristics
Measurement MethodTrue RMS
Input Voltage Range0–24 V AC / 0–500 V AC / Customized
Continuous Overload Current10 A AC (verify)
Input Signal Frequency40–100 Hz
Sampling Frequency31 kHz (typical)
Conversion AccuracyMax. 1.0% error at nominal input, 25°C
Response Time100 ms (typical)

Output Characteristics

Output Characteristics
Analog Current Output4–20 mA / 0–20 mA
Analog Voltage Output0–5 V / 0–10 V / 1–5 V / 2–10 V
Max. Output Load — Current Output700 Ω at 24 V DC supply
Min. Output Load — Voltage Output10 Ω (verify)
Output Load ErrorMax. 5% error (datasheet wording; verify)

Operating Conditions

Operating Conditions
Operating Temperature-10°C to +60°C

Mechanical Characteristics

Mechanical Characteristics
MountingDIN rail
DimensionsRefer to dimensional drawing

Full certificate register

Ready To Specify Your Next Project?

Our sales engineers work directly with panel builders and procurement teams to specify the right product, confirm lead times, and coordinate international shipping.

VT Series — Single-Phase Voltage Transducer — VTEKE